Generator set model | MGS2000R |
---|---|
Generator voltage (V) | 380 |
Frequency (Hz) | 50 |
Generator output (kVA) | 1800 |
Generator output (kW) | 1440 |
Duty | Prime |
Rating Prime | Prime |
Average load factor for 24h | Maximum 80%Overload operation (<110%) islimited to a maximum of 1 hourper 12 hoursOver 90% load operation limitedto a maximum of 3 hours per 24hours |
Overload | +10%Overload |
Installation location | Indoor |
General information
The MGS are designed by Mitsubishi Heavy Industries Engine System Asia (MHIES-A), following Japanese refined standards. These generator sets are manufactured complying to the highest quality standards (ISO 9001:2015), in Singapore and Vietnam. MGS is offered through various combinations and additional options for customization and fine tuning for any technical specification and requirements to meet your needs. The durability and reliability of our generator sets make it suitable for all kinds of applications such as: construction, healthcare, commercial municipal buildings, industrial usage, independent power plants, agriculture, and factories. The rating definitions are compliant with ISO8528-1 from Emergency Standby Power (ESP), Prime Rated Power (PRP), and Continuous Operating Power (COP).
Benefits
- Mitsubishi made premium product
- Easy maintenance and operation
- Reliable and high quality
- Robust performance
Engine model | S16R-PTAR |
---|---|
Engine speed (rpm) | 1500 |
Engine brake output (kWm) | 1553 |
Turbocharged | 4 cycle, direct injection,turbocharged with aircooler |
Governor | Digital Electrical type |
Cooling method | Centrifugal type driven by engine |
Starting method | Starter motor capacity : 7.5kW x 2 (DC24V) |
*This data may be revised without prior notice. All pictures shown are for illustration purpose only.